Emergency Rental Boiler

Clinton, Iowa

When a rendering plant in Clinton, Iowa needed steam fast, our Iowa Boiler Rental team delivered. Less than 24 hours after the initial call, we had a 1,000 HP trailer-mounted firetube boiler on-site, set up, and producing steam. This quick turnaround helped the facility avoid major downtime and keep operations moving.

Boiler Specs:

  • Size/Type: 1,000 HP firetube, trailer-mounted

  • Fuel: Natural gas, 4" 150# flanged connection

  • Operating Pressure: 135 psi (150 psi MAWP)

  • Steam Outlet: 6" 300# flanged, with 8"x6" ASME reducing spool

  • Feedwater: 2" 300# flanged modulating

  • Blowdown: 2" FIP connection

  • Valves: 8" 300# flanged angle non-return and stop valves

  • Relief Valves: Four safety relief valves set at 150 psi, with discharge piping (shipped loose)

  • Electrical: 480V / 3-phase / 200 amp, single-point, non-fused disconnect

  • Stack: Stub stack included

What We Handled:

  • Fast mobilization and transport

  • Full setup and on-site commissioning

  • Support through inspection and compliance checks

This project is a great example of our ability to move quickly when customers need it most—delivering reliable steam power with minimal disruption.

  • Boiler Rentals

SCHEDULE YOUR SERVICE TODAY!

GET THE HELP YOU NEED FOR ALL THINGS MECHANICAL