Emergency Rental Boiler
Clinton, Iowa

When a rendering plant in Clinton, Iowa needed steam fast, our Iowa Boiler Rental team delivered. Less than 24 hours after the initial call, we had a 1,000 HP trailer-mounted firetube boiler on-site, set up, and producing steam. This quick turnaround helped the facility avoid major downtime and keep operations moving.
Boiler Specs:
Size/Type: 1,000 HP firetube, trailer-mounted
Fuel: Natural gas, 4" 150# flanged connection
Operating Pressure: 135 psi (150 psi MAWP)
Steam Outlet: 6" 300# flanged, with 8"x6" ASME reducing spool
Feedwater: 2" 300# flanged modulating
Blowdown: 2" FIP connection
Valves: 8" 300# flanged angle non-return and stop valves
Relief Valves: Four safety relief valves set at 150 psi, with discharge piping (shipped loose)
Electrical: 480V / 3-phase / 200 amp, single-point, non-fused disconnect
Stack: Stub stack included
What We Handled:
Fast mobilization and transport
Full setup and on-site commissioning
Support through inspection and compliance checks
This project is a great example of our ability to move quickly when customers need it most—delivering reliable steam power with minimal disruption.